OmniLink II
OmniLink II
Press Automation
Control
OPERATING MANUAL
Version 1.0
LINK ELECTRIC & SAFETY CONTROL COMPANY
444 McNALLY DRIVE, NASHVILLE TN 37211
PH (615)-833-4168 FAX (615)-834-1984
Przeglądanie stron 0
1 2 3 4 5 6 ... 153 154

Podsumowanie treści

Strona 1 - OmniLink II

OmniLink IIOmniLink IIPress AutomationControlOPERATING MANUALVersion 1.0LINK ELECTRIC & SAFETY CONTROL COMPANY444 McNALLY DRIVE, NASHVILLE T

Strona 2

August 30, 2002 Manual Version 1.0 2.1Section 2 Installation Section 2.1 Preliminary Installation Considerations 1. Before you begin to install

Strona 3

August 30, 2002 Manual Version 1.0 5.17 StrokeModeSingle StrokeDriveSpeedStrokeSpeedSPMSPM2000OrderCounterPC STATUSCounter OFFQUICKACCESSEDITNOTES00

Strona 4

August 30, 2002 Manual Version 1.0 5.18 In order for the job notes to be saved after editing, the current job must be stored. Job storage is descri

Strona 5

August 30, 2002 Manual Version 1.0 5.19 The display provides the following information: 1. A list of all jobs presently in the internal file stora

Strona 6 - Section 1 Introduction

August 30, 2002 Manual Version 1.0 5.20 Section 5.6.2 Recall Setup From the Jobs Menu, Figure 5.9, pressing the RECALL SETUP softkey will either tr

Strona 7

August 30, 2002 Manual Version 1.0 5.21 Section 5.6.3 Erase Setup From the Jobs Menu, Figure 5.9, pressing the RECALL SETUP softkey will either tra

Strona 9 - DEVELOPED

August 30, 2002 Manual Version 1.0 6.1 Section 6 Digital Die Protection and Process Monitor The Digital Die Protection and Process Monitor Module

Strona 10 - Section 2 Installation

August 30, 2002 Manual Version 1.0 6.2 If the monitor detects a process fault, a stop signal will be sent to the press control. There are three typ

Strona 11

August 30, 2002 Manual Version 1.0 6.3 PARAMETER SPECIFICATION Enclosure Dimensions 11.9” (302 mm) High x 6.25” (159 mm) Wide x 4” (102 mm) Deep

Strona 12

August 30, 2002 Manual Version 1.0 6.4 17856234PROCESS MONITORDIE PROTECTION &12 43576891110 141312 1615MODEL 512xLINKERROR CODEMODULE NUMBER /

Strona 13

August 30, 2002 Manual Version 1.0 2.2It is also convenient to run the 115VAC power along with the high-speed serial bus cable to each module(s) enc

Strona 14 - OmniLink II LCD

August 30, 2002 Manual Version 1.0 6.5 Section 6.4 Wiring The wiring diagram for Model 5020 units is shown in Figure 6.2. The wiring diagram for M

Strona 15 - CRANK OR ECCENTRIC

August 30, 2002 Manual Version 1.0 6.6 DIE PROTECTION &PROCESS MONITOR765123LINK14MODEL 51202365886442753178910151112131416 Figure 6.2 Model 51

Strona 16 - MODULE ENCLOSURE

August 30, 2002 Manual Version 1.0 6.7 DIE PROTECTION &PROCESS MONITOR765123LINK14MODEL 51212365886442753178 Figure 6.3 Model 5121 Wiring Diagr

Strona 17 - Section 2.3.1 Conduit Runs

August 30, 2002 Manual Version 1.0 6.8 Since there can be up to five Digital Die Protection and Process Monitors connected to each OmniLink II Press

Strona 18

August 30, 2002 Manual Version 1.0 6.9 mechanical sensors. For these sensors, it may be necessary to source more current through the sensors than r

Strona 19 - CONNECTION FOR CLOCKWISE

August 30, 2002 Manual Version 1.0 6.10 V+SIGNALCOMV+SIGNALCOM24 VDC0 VDCTO INPUTNPN CONNECTIONSV+SIGNALCOMV+SIGNALCOM24 VDC0 VDCTO INPUTSERIESPARAL

Strona 20

August 30, 2002 Manual Version 1.0 6.11 Static Normally Off, the input should NOT be On under normal operation. In this case when the input switche

Strona 21

August 30, 2002 Manual Version 1.0 6.12 Section 6.5.2 Cyclic Cyclic inputs are derived from monitored events that occur once each machine cycle wh

Strona 22 - SECONDARY WINDING

August 30, 2002 Manual Version 1.0 6.13 Sensors that are used as inputs to cyclic channels can be either Normally On or Normally Off. The event is

Strona 23

August 30, 2002 Manual Version 1.0 6.14 Section 6.5.3 In Position In Position type channels are used to monitor whether material is fully fed int

Strona 24

August 30, 2002 Manual Version 1.0 2.34. NEVER use any cable other than that supplied by Link Systems for the high-speed serial bus that interconne

Strona 25 - PRESS CONTROL

August 30, 2002 Manual Version 1.0 6.15 Figure 6.10 also shows some unacceptable conditions for In Position events. There are three unacceptable co

Strona 26

August 30, 2002 Manual Version 1.0 6.16 Section 6.5.4 One Part Detection Edge The One Part Detector Edge channel logic type is used to monitor eje

Strona 27

August 30, 2002 Manual Version 1.0 6.17 past the sensor. An example of One Part Detector Pass is shown in Figure 6.13. This example shows an exiti

Strona 28

August 30, 2002 Manual Version 1.0 6.18 part is totally out of the die area. The Two Part Detector Edge input type functions much like the One Pa

Strona 29 - SS RELAY MODULE

August 30, 2002 Manual Version 1.0 6.19 The Two Part Detector Pass input type timing requires that the input sensor detect both parts during the tim

Strona 30

August 30, 2002 Manual Version 1.0 6.20 angle just before the part is released into the next stage of the die. The timing for Transfer is shown in F

Strona 31 - Customer’s Enclosure

August 30, 2002 Manual Version 1.0 6.21 Section 6.6 Configuration In order for the Digital Die Protection and Process Monitor to be recognized by

Strona 32 - (Optional)

August 30, 2002 Manual Version 1.0 6.22 Section 6.6.1 Reset All Channels Configuration There are two options to Reset Configuration. These option

Strona 33

August 30, 2002 Manual Version 1.0 6.23 When bypassed, the system will halt all monitoring functions. See Section 6.7 for more information concerni

Strona 34 - OmniLink II LCD

August 30, 2002 Manual Version 1.0 6.24 StrokeModeDriveSpeedStrokeSpeedSPMSPM00OrderCounterSYSTEM STATUSCounter OFFDieProtectionCHANGESETTINGEXIT00P

Strona 35

August 30, 2002 Manual Version 1.0 2.4Section 2.2 Mounting System Components Section 2.2.1 Mounting the Operator Terminal Enclosure The OmniLink I

Strona 36 - Section 3.3 Softkeys

August 30, 2002 Manual Version 1.0 6.25 Section 6.7.1 Channel Settings The channel settings define the monitoring type of the channel and the param

Strona 37 - Section 3.6 Arrow keys

August 30, 2002 Manual Version 1.0 6.26 Channel Type Description Section for Additional Information Static Channel type used to monitor sensor

Strona 38 - Screen Legend

August 30, 2002 Manual Version 1.0 6.27 programmed names as required. It must be noted that when a job is stored in memory, only the number assigne

Strona 39 - SoftKeys

August 30, 2002 Manual Version 1.0 6.28 remains in the fault condition for the length of the delay time, a fault will be issued. If the channel ret

Strona 40

August 30, 2002 Manual Version 1.0 6.29 Diagnostics screen. A sample of the Die Protection Channel Diagnostics screen is shown in Figure 6.24. This

Strona 41

August 30, 2002 Manual Version 1.0 6.30 options range from bypassing individual channels to bypassing the entire system. Section 6.7.3.1 Channel By

Strona 42

August 30, 2002 Manual Version 1.0 6.31 Section 6.7.3.4 Bypass in Setup Mode and Bypass on Job Recall Individual channels can be automatically bypa

Strona 43

August 30, 2002 Manual Version 1.0 6.32 one time. The Reset can be configured to only reset the channels that are displayed on one Die Protection s

Strona 44

August 30, 2002 Manual Version 1.0 7.1 Section 7 Programmable Limit Switch (PLS) The Programmable Limit Switch is an optional addition to the Omni

Strona 45 - ACCESS CODE

August 30, 2002 Manual Version 1.0 7.2 PARAMETER SPECIFICATION 5100-5B Module Dimensions without Enclosure 10.4” (264 mm) High x 5.5” (138 mm) Wid

Strona 46 - (Pasword)for

August 30, 2002 Manual Version 1.0 2.5 Figure 2.5 Dimensions for Mounting OmniLink II LCD Operator Terminal Section 2.2

Strona 47

August 30, 2002 Manual Version 1.0 7.3 Figure 7.1 PLS 5100-5B Open Frame Mounting

Strona 48

August 30, 2002 Manual Version 1.0 7.4 Figure 7.2 PLS Enclosure Mounting

Strona 49

August 30, 2002 Manual Version 1.0 7.5 Section 7.4 Wiring The wiring diagram for Programmable Limit Switch units is shown in Figure 7.3. The follo

Strona 50

August 30, 2002 Manual Version 1.0 7.6 Figure 7.3 PLS Wiring Diagram

Strona 51 - AUXILIARY

August 30, 2002 Manual Version 1.0 7.7 Section 7.4.4.1 Electromechanical Relay Wiring Each electromechanical relay has both normally open and nor

Strona 52

August 30, 2002 Manual Version 1.0 7.8 In addition to being the desired setting for an unused channel, Always Off mode has another potential use.

Strona 53 - PREVIOUS

August 30, 2002 Manual Version 1.0 7.9 programmed for counted outputs with a count of four, the channel will not turn on every stroke, but only turn

Strona 54

August 30, 2002 Manual Version 1.0 7.10 example, a feed roll pilot release is intended to release the feed rolls from the material, so that the die

Strona 55

August 30, 2002 Manual Version 1.0 7.11 The Programmable Limit Switch system should be configured before being put into operation. This configurati

Strona 56

August 30, 2002 Manual Version 1.0 7.12 Section 7.6.1 Reset All Channels Configuration There are two options to Reset Configuration. These option

Strona 57

August 30, 2002 Manual Version 1.0 2.6The standard resolver used with the OmniLink II press Automation Control is the 2500 Resolver. A 5000 Resolve

Strona 58

August 30, 2002 Manual Version 1.0 7.13 abcdbaeStrokeModeDriveSpeedStrokeSpeedSPMSPM00OrderCounterSYSTEM STATUSCounter OFFLimitSwitchCHANGECHANNELSE

Strona 59 - & 360

August 30, 2002 Manual Version 1.0 7.14 Section 7.7.1 Channel Settings The channel settings define the mode of the channel and the parameters assoc

Strona 60

August 30, 2002 Manual Version 1.0 7.15 Channel Type Description Section for Additional Information Always Off Channel output is always turned of

Strona 61

August 30, 2002 Manual Version 1.0 7.16 Section 7.7.1.4 Counted Outputs This parameter allows for the PLS channel to be programmed for counted outp

Strona 62

August 30, 2002 Manual Version 1.0 7.17 Section 7.7.3 Status Information Status information is available for the individual channel, the individua

Strona 63

August 30, 2002 Manual Version 1.0 2.7 Figure 2.8 Mounting Dimensions for 8 or 16 Channel Die Protection or Si

Strona 64 - SPM Input Cal # :

August 30, 2002 Manual Version 1.0 2.8Section 2.3 Wiring System Modules and Components Section 2.3.1 Conduit Runs Wiring between the enclosures fo

Strona 65

August 30, 2002 Manual Version 1.0 2.9The conduit runs that you will or may need, depending on the options you purchase and features that you wish t

Strona 66

August 30, 2002 Manual Version 1.0 2.10 Figure 2.10. Wiring Connections from 2500 Resolver to 802-5 R

Strona 67

August 30, 2002 Manual Version 1.0 iSection 1 Introduction...1.1 Sect

Strona 68

August 30, 2002 Manual Version 1.0 2.11 Figure 2.11. Wiring Connections from 5000 Resolver to 802-5 R

Strona 69

August 30, 2002 Manual Version 1.0 2.12Section 2.3.3 Wiring 115VAC Power From Press Control to Operator Terminal Pull red, white and green 16 gauge

Strona 70

August 30, 2002 Manual Version 1.0 2.13 Figure 2.13 115VAC Wiring Between Press Control and Operator

Strona 71

August 30, 2002 Manual Version 1.0 2.14Section 2.3.4 Wiring the Valve Voltage Circuit The OmniLink II Press Automation Control brake monitor and mo

Strona 72

August 30, 2002 Manual Version 1.0 2.15 Figure 2.14 Stop Circuit Connections from OmniLink II Automatio

Strona 73

August 30, 2002 Manual Version 1.0 2.16Section 2.3.6 Wiring the Optional Setup Mode Input The OmniLink II Press Automation Control provides an opti

Strona 74

August 30, 2002 Manual Version 1.0 2.17Section 2.3.7 Wiring Optional Analog Input/Output Board Circuits Section 2.3.7.1 Wiring to Display Motor Loa

Strona 75

August 30, 2002 Manual Version 1.0 2.18 Figure 2.16 Wiring the Analog Motor Load Current Input Tra

Strona 76

August 30, 2002 Manual Version 1.0 2.19 Figure 2.17 Wiring to Display and Set SPM Through OmniLink II O

Strona 77

August 30, 2002 Manual Version 1.0 2.20Section 2.3.8 Optional Solid State Relay Outputs The OmniLink II Press Automation Control provides an option

Strona 78

August 30, 2002 Manual Version 1.0 iiSection 4.2.1.8 Setting Brake Monitor Top Stop and Brake Monitor Mid Stroke Stop Limits ...

Strona 79

August 30, 2002 Manual Version 1.0 2.21Section 2.4 Additional Mounting and Wiring if the Operator Terminal, R/D-Brake Monitor Module, and (Optionall

Strona 80

August 30, 2002 Manual Version 1.0 2.22 Section 2.4.2 Wiring the Base Components in the Customer Enclosure The only wiring not

Strona 81

August 30, 2002 Manual Version 1.0 2.23in separate documents sent in addition to this manual when these options are purchased with your system. Sec

Strona 83

August 30, 2002 Manual Version 1.0 3.1Section 3 Operator Terminal Basics Section 3.1 OmniLink II Press Automation Control LCD Operator Terminal

Strona 84

August 30, 2002 Manual Version 1.0 3.2stopped within +/- 5 degrees of bottom dead center, the box will be yellow with the letters “BOT”. For speeds

Strona 85

August 30, 2002 Manual Version 1.0 3.3choose to configure the system to allow certain commonly used settings and actions to be done in Run Mode. Fin

Strona 86 - Section 5.2.1 Brake Monitor

August 30, 2002 Manual Version 1.0 3.4Section 3.5 CHG Key This changes the display language from English to Spanish. Depressing the CHG key again w

Strona 87

August 30, 2002 Manual Version 1.0 3.5keys on the keypad and pressing the ENT (Enter) key after you have changed the number to the desired value. T

Strona 88

August 30, 2002 Manual Version 1.0 3.6 Figure 3.3 The Die Protection Channel Settings Screen in Program Mode When the Channel T

Strona 89

August 30, 2002 Manual Version 1.0 iiiSection 5.6.2 Recall Setup ...

Strona 90 - Section 5.2.8 Diagnostics

August 30, 2002 Manual Version 1.0 3.7 Figure 3.5 The Die Protection Channel Names Screen The first page of names for the Die Pr

Strona 91

August 30, 2002 Manual Version 1.0 3.8This illustration is for the Die Protection Channel Names Screen that will be present if one or more optional

Strona 92 - Section 5.3 Counters

August 30, 2002 Manual Version 1.0 3.9means available to access Program Mode. All settings and actions for the system are accessible to anyone when

Strona 93

August 30, 2002 Manual Version 1.0 3.10 Figure 3.7 Main Die Protection Screen in Run Mode for Module 1, Channels 1-8

Strona 94

August 30, 2002 Manual Version 1.0 3.11Section 3.9.3 Code (Password) System Operation If any of the access modes to Program Mode that use a code is

Strona 95 - Section 5.3.3 Scrap Counter

August 30, 2002 Manual Version 1.0 3.12module) and a group of eight channels for that module. One module may have up to 16 channels. The PREVIOUS PA

Strona 96

August 30, 2002 Manual Version 1.0 3.13 Figure 3.11 User Selection Box Appears on Die Protection Configuration Screen

Strona 97

August 30, 2002 Manual Version 1.0 3.14 Figure 3.13 Die Protection Channels Settings Program Mode Screen . To perform a reset

Strona 98

August 30, 2002 Manual Version 1.0 3.15new 60 second cycle will be started. The number of strokes that are entered is the number of press strokes a

Strona 101 - Section 5.5.5 LOGOUT Softkey

August 30, 2002 Manual Version 1.0 4.1 Section 4 Device and Main Configuration Menus After your OmniLink II Press Automation Control is first ins

Strona 102 - Section 5.6.1 Store Setup

August 30, 2002 Manual Version 1.0 4.2 The Device Configuration menu is also used to update the software in the various modules used with the system

Strona 103 - Section 5.6.2 Recall Setup

August 30, 2002 Manual Version 1.0 4.3 The left column of the Device Configuration screen lists hardware modules that can be used with the system.

Strona 104 - Section 5.6.3 Erase Setup

August 30, 2002 Manual Version 1.0 4.4 Pressing the NEXT PAGE softkey causes the second page of the Device Configuration menu to be displayed, as sh

Strona 105

August 30, 2002 Manual Version 1.0 4.5 4. Configuring the Operator Terminal serial ports for any software options, such as serial feed interface an

Strona 106

August 30, 2002 Manual Version 1.0 4.6 If the CONFIGURE softkey is pressed, the display will ask for the configuration code. This user configuration

Strona 107

August 30, 2002 Manual Version 1.0 4.7 Section 4.2.1 Machine Parameters Menu Pressing the Machine Parameters softkey in the Main Configuration menu

Strona 108 - Section 6.3 Mounting

August 30, 2002 Manual Version 1.0 4.8 top on the Machine Parameters menu. This setting comes from the factory as 00 since it is most likely that y

Strona 109 - MODEL 512x

August 30, 2002 Manual Version 1.0 4.9 If the loss of motion time value calculated by the formula is not longer than the time that motion can dip be

Strona 110 - Section 6.4 Wiring

August 30, 2002 Manual Version 1.0 4.10 Method 1. Slide at Top of Stroke 1. Inch the press to position the crankshaft within +/- 1 degrees of top

Strona 111

August 30, 2002 Manual Version 1.0 1.1Section 1 Introduction The OmniLink II Press Automation Control for part revolution clutch mechanical power

Strona 112

August 30, 2002 Manual Version 1.0 4.11 Thus, regardless of whether you have a negative or positive misalignment of encoder to crankshaft, the Encod

Strona 113

August 30, 2002 Manual Version 1.0 4.12 Section 4.2.1.6 Use Mode Input Setting The OmniLink II Press Automation Control provides an input that allo

Strona 114

August 30, 2002 Manual Version 1.0 4.13 be accommodated so that adjustment on a frequent basis is not necessary. A typical wear margin of 20% is us

Strona 115 - Section 6.5.1 Static

August 30, 2002 Manual Version 1.0 4.14 3. Take the longest stop time recorded in step 2 and add a 10% to 20% margin for wear and other factors tha

Strona 116

August 30, 2002 Manual Version 1.0 4.15 Figure 4.10 Speed/Load Configuration Menu Section 4.2.2.1 Setting Speed Mode If you hav

Strona 117 - Section 6.5.2 Cyclic

August 30, 2002 Manual Version 1.0 4.16 Use the arrow keys to select your choice of 3 Speed Mode settings; Input Only, Output Without Recall, or Out

Strona 118 - UNACCEPTABLE

August 30, 2002 Manual Version 1.0 4.17 6. Select the CONTINUOUS stroking mode on the press stroking selector and initiate press stroking. 7. The

Strona 119 - MATERIAL

August 30, 2002 Manual Version 1.0 4.18 2. Return to the Speed/Load Configuration menu and set Speed Mode to Output Without Recall or Output With R

Strona 120

August 30, 2002 Manual Version 1.0 4.19 6. Observe the Stroke Speed indicator at the top of the operator terminal display. This is the true strokin

Strona 121 - One Part-Edge

August 30, 2002 Manual Version 1.0 4.20 Section 4.2.2.5 Calibrating Percent Motor Load If an input signal is provided to the OmniLink Analog Input/

Strona 122 - One Part-Pass

August 30, 2002 Manual Version 1.0 1.2Section 1.1.2 Base System Optional Features • An optional analog input/output card allows stroking speed to

Strona 123 - Two Part-Edge

August 30, 2002 Manual Version 1.0 4.21 Figure 4.12 Speed Adjusted Top Stop Calibration Menu There are 7 items indicated

Strona 124 - Two Part-Pass

August 30, 2002 Manual Version 1.0 4.22 6. Calculated Degrees Before Top Dead Center. For variable speed presses, the OmniLink II Press Automation

Strona 125 - Section 6.5.9 Custom

August 30, 2002 Manual Version 1.0 4.23 to Program so that you can change the settings made in step 3. If the press has stopped X degrees beyond Top

Strona 126 - Section 6.6 Configuration

August 30, 2002 Manual Version 1.0 4.24 It is IMPORTANT TO NOTE that the OmniLink II cannot provide Auto Top Stop Compensation for top stop signals

Strona 127

August 30, 2002 Manual Version 1.0 4.25 5. The stopping time and distance (angle) for the press may be different depending on the angular region ov

Strona 128 - Section 6.7 Operation

August 30, 2002 Manual Version 1.0 4.26 Continuous mode at various speeds between the low and high speeds. For each speed, press the Top Stop key a

Strona 129

August 30, 2002 Manual Version 1.0 4.27 7. Counterbalance Pressure. If the control is equipped with optional automatic counterbalance adjust 8. Shut

Strona 130

August 30, 2002 Manual Version 1.0 4.28 Figure 4.14 Code Entry Screen to Zero Stroke Count Entering the two digit code sent for

Strona 131

August 30, 2002 Manual Version 1.0 4.29 4. Those settings and operations that the system always requires Key/Code access to Program Mode to make.

Strona 132

August 30, 2002 Manual Version 1.0 4.30 the Access Configuration screen shown in Figure 4.15. The Restrict/Unrestrict configuration screen shown in

Strona 133

August 30, 2002 Manual Version 1.0 1.3Section 1.3 System Overview Figure 1.1 shows the base package hardware components for the OmniLink II Press Au

Strona 134 - Section 6.7.3 Bypass

August 30, 2002 Manual Version 1.0 4.31 The stroke log out is based upon a number of press strokes between keyboard activity. If the user does not

Strona 135

August 30, 2002 Manual Version 1.0 4.32 Note! The list of permissions shown on the screen is shown as an example. New software versions and hardware

Strona 136 - Section 6.7.4 Reset

August 30, 2002 Manual Version 1.0 4.33 Section 4.2.4.4 Auxiliary Communications Setup The AUXILIARY COMM. SETUP softkey provides access to the con

Strona 137

August 30, 2002 Manual Version 1.0 4.34 To enter the alpha-numeric messages associated with each input message code (number) go to the Auxiliary Nam

Strona 138 - Section 7.2 Specifications

August 30, 2002 Manual Version 1.0 5.1 Section 5 Using the OmniLink II Press Automation Control Standard Functions and Optional Speed Adjust Functi

Strona 139 - Section 7.3 Mounting

August 30, 2002 Manual Version 1.0 5.2 Figure 5.1 Main Menu of the Operator Terminal Section 5.2 Brake Monitor and Diagn

Strona 140

August 30, 2002 Manual Version 1.0 5.3 The central portion of the display provides the following information: 1. A brake monitor used when the pre

Strona 141

August 30, 2002 Manual Version 1.0 5.4 WARNING! When your press is equipped with two-hand control devices and/or presence sensing device

Strona 142 - Section 7.4.4 Output Wiring

August 30, 2002 Manual Version 1.0 5.5 on where in the stroking cycle the fault occurs and how many degrees the press crankshaft will travel after t

Strona 143

August 30, 2002 Manual Version 1.0 5.6 The Intellistop angle is automatically computed by the OmniLink based on the angle of travel during top stopp

Strona 144

August 30, 2002 Manual Version 1.0 1.4 Figure 1.2. Existing and Planned System Components and Functi

Strona 145 - Section 7.5.4 Timed Off Mode

August 30, 2002 Manual Version 1.0 5.7 Section 5.2.5 Auxiliary Equipment Messages The OmniLink II Press Automation Control makes optional provision

Strona 146 - Section 7.5.5 Toggle Mode

August 30, 2002 Manual Version 1.0 5.8 Figure 5.4 Diagnostics Screen The softkeys along the bottom of the screen navigate to ot

Strona 147 - Section 7.6 Configuration

August 30, 2002 Manual Version 1.0 5.9 Section 5.3 Counters From the Main Menu, Figure 5.1, depressing the COUNTER softkey displays the menu shown

Strona 148

August 30, 2002 Manual Version 1.0 5.10 in the counter configuration. If an auxiliary counter is enabled in the counter configuration, it will appe

Strona 149 - Section 7.7 Operation

August 30, 2002 Manual Version 1.0 5.11 access Program Mode in order to turn the counters on or off. If the user accesses Program Mode by using the

Strona 150

August 30, 2002 Manual Version 1.0 5.12 have permission to change counter settings. To increase or decrease the current count value by one, select

Strona 151

August 30, 2002 Manual Version 1.0 5.13 To change the value of the scrap count, position the cursor on the scrap counter and select the CHANGE SCRAP

Strona 152

August 30, 2002 Manual Version 1.0 5.14 Batch, and Quality counters are fixed and cannot be programmed. To change an auxiliary counter name, posi

Strona 153 - Section 7.7.2 Reset

August 30, 2002 Manual Version 1.0 5.15 Section 5.3.4.4 Configure Counter Reset When Order Counter Reset All counters other than the Order counter

Strona 154

August 30, 2002 Manual Version 1.0 5.16 higher than 80 SPM when INCH mode is selected. If the press control is configured for fixed setup (INCH) mo